1000 VA / 800 W |
2000 VA / 1600 W |
3000 VA / 2400 W |
6000 VA / 4800 W |
10000 VA / 8000 W |
Single phase with ground |
INPUT |
55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or
160-280VAC (Based on load at 100%) |
110-300 VAC (Based on load at 50%); 176-300 VAC (Based on load at
100%) |
100/110/115/120/127VAC or 200/208/220/230/240VAC |
208/220/230/240 VAC |
40Hz ~70 Hz |
46~54 Hz or 56~64 Hz |
≧ 0.99 @ Nominal Voltage (100% load) |
OUTPUT |
± 1% |
100/110/115/120/127VAC or 200/208/220/230/240VAC |
208/220/230/240 VAC |
50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
50 Hz or 60 Hz ± 0.1 Hz |
Zero |
4 ms (Typical) |
Zero |
Pure Sine Wave |
3:1 |
≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) |
≦ 3% THD (Linear Load); ≦ 5% THD (Non-linear Load) |
47~53 Hz or 57~63 Hz |
46~54 Hz or 56~64 Hz |
EFFICIENCY |
83% |
87% |
88% |
90% |
91% |
88% |
89% |
90% |
92% |
93% |
BATTERY |
Depending on the capacity of external batteries |
1A/2A/4A/6A (Adjustable) |
1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries) |
27.4 VDC ± 1%, 41.0 VDC ± 1% |
54.7 VDC ± 1%, 82.1 VDC ± 1%, 109.4VDC ±1% |
82.1 VDC ± 1% ,109.4 VDC ± 1% |
273 VDC ± 1% (Based on 20pcs bateries) |
2, 3 |
4, 6, 8 |
6, 8 |
16~20 (Adjustable) |
12 V / 9 AH |
12 V / 9 Ah |
1A |
1A/2A |
27.4 VDC ± 1% |
54.7 VDC ± 1% |
82.1 VDC ± 1% |
218.4 VDC ± 1% , 273 VDC ± 1% |
2 |
4 |
6 |
16, 20 |
4 hours recover to 90% capacity |
9 hours recover to 90% capacity |
INDICATORS |
Load level, Battery level, AC mode, Battery mode, Bypass mode, and
Fault indicators |
ALARM |
Sounding every 4 seconds |
Sounding every second |
Sounding twice every second |
Continuously sounding |
ENVIRONMENT |
20~90% RH @ 0- 40°C (non-condensing) |
0~95% RH @ 0- 50°C (non-condensing) |
0~95% RH @ 0- 40°C (non-condensing) |
PHYSICAL |
282 x 145 x 220 |
397 x 145 x 220 |
421 x 190 x 318 |
369 x 190 x 688 |
9.8 |
17 |
27.6 |
61, 74 |
66 , 76 |
282 x 145 x 220 |
397 x 145 x 220 |
369 x 190 x 318 |
442 x 190 x 318 |
4.1 |
6.8 |
7.4 |
12 |
16 |
ENVIRONMENT |
Less than 50dB @ 1 Meter |
Less than 55dB @ 1 Meter |
Less than 58dB @ 1 Meter |
MANAGEMENT |
Power management from SNMP manager and web browser |
Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Reviews