NU33RM Modular Series Online UPS 25-200kVA

Call for price

The NU33 Rack Mounted Modular Series UPS is scale-able, hot-swap-able, online double conversion. The power capacity is from 25 to 200kVA/kW.

Description

The NU33 Rack Mounted Modular Series UPS is scalable, hot-swappable, online double conversion. The power capacity is from 25 to 200kVA/kW, it’s the ideal choice for modern data center. With the latest IGBT three-level and full DSP control technology, the new RM (Rack mounted) series delivers the best combination of reliability and flexibility.

APPLICATIONS

IDC(Internet Data Center), network servers and workstation, control system, communication system, office, PC etc

Main Feature

• High Power Density
25kVA power module in 2U height, saving great amount of space, easy for capacity expansion

• Rack Modular Design
Module design, compatible with 19” standard rack cabinet, convenient to be integrated with servers

• Battery Cold Start
UPS can be powered on from the battery without utility

• Friendly Interface
Touch LCD display with abundant information

SPECIFICATIONS

MODEL NU33RMS0150 NU33RMS200
System Capacity 150kVA/150kW 200KVA/200kW
Power Module Capacity 25kVA/25kW
Input Dual Input Optional                                                           Standard
Phase 3 Phase+Neutral+Ground, 380V/400V/415V(line-line)
Input Voltage Range 304~478Vac (line-line),full load;228V~304Vac (line-line),load decreases linearly according to the min phase voltage
Rate Frequency 50/60Hz
Input Frequency Range 40Hz~70Hz
Input PF >0.99
Input THDi <3% (100% Linear load)
Bypass Rate Voltage 380/400/415VAC  (line-line)
Rate Frequency 50/60Hz
Input Voltage Range Settable, -40%~+25%
Bypass Frequency Range Settable, ±1Hz, ±3Hz, ±5Hz
Bypass Overload 110% long term operation; 125% for 5 mins ;150% for 1 min; >150% for 1s
Output Rate Voltage 380/400/415VAC  (line-line)
Voltage Regulation ±1(0~100% linear load)
Rate Frequency 50/60Hz
Frequency Precision 0.1%
Output PF 1
Output THDu <1% , Linear load; <6%, Non-linear load
Crest Factor 3:1
Inverter Overload 110% for 1 hour; 125% for 10 mins ;150% for 1 min; >150% for 200 ms
Battery Voltage ±240VDC
Battery Number 40pcs (Settable: even number from 32 to 44)±1%
Voltage Precision
Charge Power up to 20% * Output active power
Battery Cold Start Standard
System Efficiency AC Mode 96.0%
ECO Mode 98.0%
Battery Mode 95.5%
Display 7.0″ color touch screen LCD + LED + keyboard
IP Class IP 20
Interface RS232, RS485, Programmable Dry Contact
Option PDU for RM150/25C,SNMP Card, Parallel kit,SPD, LBS
Temperature Operation: 0~ 40 ℃  Storge: -40 ~70 ℃
Relative Humidity 0 ~95% Non-condensing
Altitude <1000m. Within 1000m to 2000m, power derate 1% for every 100m rise
Noise (1 meter) 65dB @ 100% load, 62dB @ 45% load
Applicable Standards Safety: IEC/EN 62040-1-1 EMC: IEC/EN 62040-2  Performance: IEC/EN 62040-3
Physical Weight (kg) Cabinet 140 160
Power module 18
Dimension W*D*H(mm) Cabinet                     482*916*931                                  482*916*1550
Power module 436*677*85